MV CABLENA2XS(F)2Y cable construction cutaway
iNKA CableCatalog product illustration

MEDIUM VOLTAGE · TECHNICAL DATASHEET

NA2XS(F)2Y

XLPE-insulated aluminium medium-voltage cable with a copper screen and waterblocking tapes.

Rated voltage
6/10 kV
Conductor
Aluminium
Insulation
XLPE

From the iNKA MV catalog · 4 product sheets

SELECT YOUR CABLE

Sizes, dimensions & ratings

Choose a configuration and cable size to view its dimensions, weight and published electrical characteristics.

11 sizes · 6/10 kV

NA2XS(F)2Y · 6/10 kV
Cable sizeNominal cross-sectionOuter diameter, approximatelymmCable weight, approximatelykg/kmCable length, approximatelymConductor DC resistance at 20 °CΩ/kmCapacitanceµF/kmCurrent in ground at 20 °C (flat)ACurrent in air at 30 °C (flat)A
24,050010001,200,19——
25,054510000,8680,21——
26,060010000,6410,23194215
28,069010000,4430,26236269
30,079010000,3200,30281327
31,088510000,2530,32318377
33,0107010000,2060,35350424
35,0121010000,1640,38393485
37,0142510000,1250,43453573
39,0163510000,1000,47507652
43,0203510000,07780,52559741

Select a size to focus on its specifications. Scroll horizontally to see every column.

  • Dimensions, weight and cable length are approximate as published. Current ratings use the catalog’s flat arrangement, ground temperature 20 °C and air temperature 30 °C.
  • — indicates a value not specified in this catalog table.
View original catalog table
1 / 4
Full size
Original iNKA NA2XS(F)2Y technical table, 6/10 kV, PDF page 18
iNKA MV catalog · page 18View original page

PRODUCT OVERVIEW

Application

For networks with sudden load changes, residential and industrial areas with high short-circuit currents, cable ducts and underground installations. The catalog describes water-blocking barriers and suitability for use in water.

Standards listed in the catalog

  • TS IEC 60502-2
  • IEC 60502-2
  • TS HD 620 S2
  • HD 620 S2
  • BS 7870

SPECIFICATIONS

Electrical & mechanical data

6/10 kV
Conductor material
Aluminium
Insulation
XLPE
Outer sheath
PE
Number of cores
1
Max. operating temperature
90 °C
Max. short-circuit temperature
250 °C for 5 seconds
Minimum bending radius
15 × cable outer diameter (D)
Maximum tensile stress
30 N/mm²
Conductor class
Class 2 according to IEC 60228
Conductor construction
Circular compacted aluminium
Outer sheath compound
PE / ST7 (IEC 60502-2)
Minimum cable-laying temperature
−5 °C (general catalog guidance; see cold-laying note)
Rated voltage U₀/U
6/10 kV

D = cable outer diameter. Refer to the stated conditions for each specification.

LAYERS & MATERIALS

Cable construction

NA2XS(F)2Y layers and conductor cutaway
  1. Circular compacted aluminium conductor, Class 2 (IEC 60228)
  2. Extruded semi-conductive conductor screen
  3. XLPE insulation
  4. Extruded bonded semi-conductive insulation screen
  5. Semi-conductive waterblocking tape
  6. Copper wire and tape screen
  7. Non-conductive swellable tape
  8. PE outer sheath

Construction & performance notes

  • Single-core construction
  • XLPE insulation
  • Bonded semi-conductive insulation screen
  • Semi-conductive waterblocking tape
  • Copper wire and tape screen
  • Non-conductive swellable tape
  • PE outer sheath

TECHNICAL DOCUMENTS

Downloads & source documents

Browse all catalogues & certificates

Product family source: iNKA MV catalog, pages 18–21.